Home5References5 Power Supply of 400 Hz – Airplane Parking
Project feautures
TOTAL POWER: 160 kVA
TRANSPORT VOLTAGE:3200 V
NETWORK LENGTH: 250 meters
LOCATION: France
YEAR: 2024
PROJECT OBJECTIVES
Powering two 90 kVA converters, 250 meters apart using existing ducts
CUSTOMERNEEDS
Use existing ducts and do not open new trenches
CUSTOMER NAME
Limoges Airport
OUR SOLUTIONS IMPLEMENTED
Create a 3200 V network, consisting of a step-up/step-down transformer unit. The 3200 V voltage allows the cable sections to be reduced to a minimum, using three 6/10 kV 1x6mm² airport cables.
MATERIAL USED
One indoor step-up substation, 160 kVA 400 V / 3200 V with a permanent on load switch departure
One watertight transformer, IP68, MODULO transformer 160 kVA 3200 V / 400 V
One outdoor cabinet, receiving the watertight transformer, cabinet equipped with one low voltage circuit breaker
CUSTOMER BENEFITS
SMALL CROSS SECTION CABLE ALLOWING THE USE OF EXISTING DUCTS
WATERPTIGHT (IP68) AND CORROSION RESISTANT TRANSFORMERS, OFFERING A LONG LIFETIME